Fire Sprinklers


Valves

Dry Sprinklers: Standard Response: Pendent


Hide...
The Globe GL Series Dry Type Pendent Sprinkler is designed for use in special applications such as freezing environments and conditions where sediment or foreign materials might accumulate in ordinary drop nipples.

The Globe GL Series Dry Type Pendent Sprinkler utilizes a frangible glass ampule sprinkler. At the ampule's rated temperature, the sprinkler opens releasing the bulb seat, causing the inner tube assembly to move, allowing spring assembly to pivot alongside the inner tube. At this time, water flows through the sprinkler and is distributed by the deflector, in an approved discharge pattern.

The Globe GL Series Dry Type Pendent Sprinkler is designed for use in special applications such as freezing environments and conditions where sediment or foreign materials might accumulate in ordinary drop nipples.

The Globe GL Series Dry Type Pendent Sprinkler utilizes a frangible glass ampule sprinkler. At the ampule's rated temperature, the sprinkler opens releasing the bulb seat, causing the inner tube assembly to move, allowing spring assembly to pivot alongside the inner tube. At this time, water flows through the sprinkler and is distributed by the deflector, in an approved discharge pattern.

Model TemperatureSeismic Esc.Wrench
GL5679
k=5.6 (80 Metric)
Thread=1" NPT
135°F (57°C), 155°F (68°C), 175°F (79°C), 200°F (93°C), 286°F (141°C)Seismic Data Sheet333010 337014 (rec.)
GL5680
k=5.6 (80 Metric)
Thread=3/4" NPT
135°F (57°C), 155°F (68°C), 175°F (79°C), 200°F (93°C), 286°F (141°C)Seismic Data Sheet333010 337014 (rec.)
GL8179
k=8.0 (115 Metric)
Thread=1" NPT
135°F (57°C), 155°F (68°C), 175°F (79°C), 200°F (93°C), 286°F (141°C)Seismic Data Sheet333010 337014 (rec.)

Finishes (click icon to view)
01 - Brass
02 - Chrome
03 - White Polyester
-
-
-
04 - Black Polyester
-
-
-
06 - Wax Coated